CNPPumps PakistanHESPAK Pvt. Ltd. Quote list0 Get a Quote
Vertical cooling-tower circulation pump

LLTS (extended shaft)

Extended-shaft vertical cooling-tower circulation pumps, DN65–DN200

Same hydraulics as LLT but with a direct-connected extended-shaft structure: the pump shaft (20Cr13 stainless) is coupled to the motor, so the mechanical seal and impeller can be serviced without moving the motor. LLTS200 (350 and 400 m³/h) is available only in this structure.

  • Flow 30–480 m³/h, head up to 12.2 m
  • Extended-shaft structure; LLTS200 is extended shaft only
  • Efficiency up to about 83% (LLTS200-10.5/15)
  • Motors 1.1–15 kW, TEFC IP55, insulation class F
LLTS (extended shaft)CNP-S-000143
Flow
Staff only
Head
Staff only
Power
1.1–15 kW
Mains
50 Hz
Models
11
Liquid temp.
-15 to +100 °C

Sizes

SizeDescriptionRated flowMax pressureMotorConnectionModels
LLTS65 Extended-shaft vertical cooling-tower circulation pump, DN65 40 m³/h 6 bar 1.1 kW Flange DN65 PN10 (GB/T17241.6 RF) 1
LLTS80 Extended-shaft vertical cooling-tower circulation pump, DN80 55 m³/h 6 bar 1.5 kW Flange DN80 PN10 (GB/T17241.6 RF) 1
LLTS100 Extended-shaft vertical cooling-tower circulation pump, DN100 80 m³/h 6 bar 2.2 kW Flange DN100 PN10 (GB/T17241.6 RF) 2
LLTS125 Extended-shaft vertical cooling-tower circulation pump, DN125 120 m³/h 6 bar 3–4 kW Flange DN125 PN10 (GB/T17241.6 RF) 2
LLTS150 Extended-shaft vertical cooling-tower circulation pump, DN150 200 m³/h 6 bar 5.5–7.5 kW Flange DN150 PN6 (GB/T17241.6 RF) 3
LLTS200 Extended-shaft vertical cooling-tower circulation pump, DN200 350 m³/h 6 bar 11–15 kW Flange DN200 PN16 (GB/T17241.6 RF) 2

Models

Filter by duty point, mains frequency or size. Click a model for its performance curve and data.

ModelSizeStagesHzMotor kWrpmkg
LLTS65-5/1.1 LLTS65150 1.1 290035
LLTS80-5/1.5 LLTS80150 1.5 290041
LLTS100-5A/2.2 LLTS100150 2.2 145070
LLTS100-5/2.2 LLTS100150 2.2 145070
LLTS125-5A/3 LLTS125150 3 145082
LLTS125-5/4 LLTS125150 4 145093
LLTS150-6A/5.5 LLTS150150 5.5 1450140
LLTS150-6/7.5 LLTS150150 7.5 1450152
LLTS150-7.5/7.5 LLTS150150 7.5 1450153
LLTS200-8.5/11 LLTS200150 11 1480340
LLTS200-10.5/15 LLTS200150 15 1480362

Performance range

Every model of the LLTS (extended shaft) range on one chart: each line is the performance curve of one model. Click a line or dot to open that model with its full data.

Logarithmic scales. Published catalogue data for clean water; the correct model for your duty is confirmed by our engineers.

Dimensions & weight

Net weight and the main dimensions of each model, in millimetres, from the catalogue. Open a model for the labelled dimension drawing.

ModelHzWeight (kg)AB1B2HA1A2d1
LLTS65-5/1.1503534010011053513017015
LLTS80-5/1.5504139010012060715019015
LLTS100-5A/2.2507056013017376216020015
LLTS100-5/2.2507056013017376216020015
LLTS125-5A/3508256014519579220024015
LLTS125-5/4509356014519579720024015
LLTS150-6A/5.55014072017523284026030015
LLTS150-6/7.55015272017523287826030015
LLTS150-7.5/7.55015372017523287826030015
LLTS200-8.5/11503401000215295109536042024
LLTS200-10.5/15503621000215295113936042024

Spare parts for LLTS (extended shaft)

Parts list of the series with the material of each part. To order, send the model code and the part you need.

Request spare parts quote
No.PartMaterialStandardApplies to
1Pump bodyCast iron HT200ASTM25B All sizes
2ImpellerStainless steel ZG07Cr19Ni9AISI304 All sizes
3O-ringNBR— All sizes
4Air-vent assemblyAssembly— All sizes
5Pump headCast iron HT200ASTM25B All sizes
6Knife type mechanical sealSC/TC— All sizes
7Pump shaftStainless steel 20Cr13AISI420 All sizes
8Motor—— All sizes

Technical data

Liquid temperature

  • -15 to +100 °C

Ambient conditions

  • Up to +40 °C

Motor

  • TEFC motor, IP55, insulation class F; 50 Hz 1×220 V, 3×380 V

Supply voltage

  • 1 x 220 V
  • 3 x 380 V

Typical applications

  • Water circulation of closed cooling towers and condensers
  • Cooling of various unit equipment
  • Large-flow, low-head duties

Pumped liquid

  • Clean, thin, non-erosive, non-flammable and non-explosive liquids without solid particles or fibres that could damage the pump mechanically or chemically. A viscous or dense liquid lowers the characteristic curve and increases energy consumption.

Data basis

  • 50 Hz, 2900 / 1450 / 1480 rpm, 20 °C clean water without foreign matter, measured at 3×380 V; use within the bold part of each curve

Performance values are taken from the published CNP catalogue data. Our engineers confirm the final selection for your liquid, temperature, supply and site before quoting.

Other cooling-tower pumps

Need a pump or a spare part?