CNPPumps PakistanHESPAK Pvt. Ltd. Quote list0 Get a Quote
Submersible sewage pump

WQ-X(I)

Submersible sewage pump, WQ-X(I) semi-flow (50 Hz)

WQ-X(I): submersible sewage pump from the CNP range. 5 models, flow 10 to 50 m³/h, head up to 12 m, motors 0.75 to 4 kW. Typical duties: sewage treatment systems for buildings, hospitals, residential areas, municipal and industrial projects; drainage and waste-water treatment; mines and prospecting. Open a model for its rated duty, dimensions and datasheet, or send us your duty and we will confirm the selection.

  • Semi-flow type with a vortex-style impeller; suited to duties that must stay free of blockage.
  • Water-cutting cable entry stops liquid reaching the motor cabinet if the cable cover is damaged
  • IPX8 class F submersible motor with thermal protector (7.5 kW and below) or leak sensor (above 11 kW)
  • Double mechanical seal in an oil chamber; hydraulic lifter keeps the seal lubricated
  • Automatic vent valve exhausts air when the pump starts
WQ-X(I)CNP-S-000149
Flow
Staff only
Head
Staff only
Power
0.75–4 kW
Mains
50 Hz
Models
5
Liquid temp.
Below 40 °C

Sizes

The 5 models of the WQ-X(I) range grouped by outlet size. Open the Models tab for every model with its performance data.

Outlet sizeHeadPowerOutletModels
DN50 outlet 8–10 m 0.75–1.5 kW DN50 2
DN65 outlet 9 m 1.5 kW DN65 1
DN80 outlet 9–12 m 2.2–4 kW DN80 2

Models

Filter by duty point, mains frequency or size. Click a model for its performance curve and data.

ModelSeriesPower kWrpmOutletkg
50WQX10-8-0.75(I)WQ-X(I) 0.752850 DN5023
50WQX12-10-1.5(I)WQ-X(I) 1.52880 DN5031
65WQX25-9-1.5(I)WQ-X(I) 1.52880 DN6536
80WQX35-9-2.2(I)WQ-X(I) 2.22880 DN8050
80WQX50-12-4(I)WQ-X(I) 42840 DN8058

Performance range

Every model of the WQ-X(I) range on one chart: each dot is the rated duty point of one model. Click a line or dot to open that model with its full data.

Logarithmic scales. Published catalogue data for clean water; the correct model for your duty is confirmed by our engineers.

Dimensions & weight

Net weight and the main dimensions of each model, in millimetres, from the catalogue. Open a model for the labelled dimension drawing.

ModelWeight (kg)Dim HDim H1Dim H2Dim FDim H3
50WQX10-8-0.75(I)2343228717721577
50WQX12-10-1.5(I)3146831718225082
65WQX25-9-1.5(I)3649034020725087
80WQX35-9-2.2(I)5054539022727590
80WQX50-12-4(I)5857541523028090

Spare parts for WQ-X(I)

Typical wear and service parts for this type of pump. The exact part, material and part number depend on the model, so send us the model code (or a nameplate photo) and we confirm and quote the right one.

PartWhat it does
Mechanical seals (motor side and pump side)Keep water out of the motor; the key service part
ImpellerPasses the liquid and solids; wears with sand and grit
O-rings and gasketsSeal the motor housing and covers
BearingsCarry the rotor; replace with the seals at overhaul
Seal-chamber oilLubricates and cools the seals; change at overhaul
Power cable and cable glandSupplies the motor; the gland must stay watertight

Generic list for this pump type; it is not a part-number catalogue for the series. Our team confirms the correct part for your model before quoting.

Specification & options

Key parameters

  • Power supply50 Hz, 3 × 380 V
  • Medium temperatureBelow 40 °C
  • pH range4–10
  • Medium densityBelow 1200 kg/m³
  • Solid / liquid ratioBelow 2 %
  • MotorIPX8, insulation class F
  • Outlet pressurePN6 flange
  • Standard cable9 m (15 m and up in 5 m steps)

Oil capacity by pump power

Pump powerOil capacityRemark
2P-0.37kW320
2P-0.55/0.75/1.1kW50040/50WQ15-8-1.1(I); 40/50WQ15-13-1.1(I); 50WQ10-15-1.1QG(I); 50WQ15-12-1.1QG(I); 40/50WQ15-13-1.1JY(I); 40/50WQ15-8-1.1JY(I)
2P-1.1kW670
2P-1.5kW940
2P-2.2kW1160
2P-3kW1100
2P-4kW1300
2P-5.5kW2140
2P-7.5/11/15kW2000
6P-22/30/37kW9100
6P-45/55/75kW14000
8P-22kW9100
4P-2.2kW1300
4P-4kW1200
4P-5.5kW4200
4P-7.5kW4500
4P-11kW5200
4P-15kW5100
4P-18.5/22kW4600
4P-30kW8600
4P-37/45kW9100
4P-55/75kW9600
4/6P-90-150kW25000

Oil capacity unit is not printed in the catalogue.

More features

  • Semi-closed / open double-channel impeller for stable running and low vibration
  • Direct starting up to 37 kW; star-delta from 45 kW; inverter or soft starter advised from 11 kW

Technical data

Liquid temperature

  • Below 40 °C

Typical applications

  • Sewage treatment systems for buildings, hospitals, residential areas, municipal and industrial projects
  • drainage and waste-water treatment
  • mines and prospecting
  • irrigation, aquaculture and fountains
  • Pumped liquid may be rainwater or waste water containing solids and long fibres

Data basis

  • CNP WQ 50 Hz catalogue E221004

Performance values are taken from the published CNP catalogue data. Our engineers confirm the final selection for your liquid, temperature, supply and site before quoting.

Other sewage & drainage pumps

WQ(I)

Submersible sewage pump

  • Flow 8–2000 m³/h
  • Head up to 60 m
  • 0.55–150 kW

Need a pump or a spare part?

Send us the flow and head you need, or the model code and nameplate details of the pump you are repairing. Our team replies with a quotation.